垂询电话:
电子邮箱:

ÖPVC-JZ/OZ ARCTIC +UV SCHWARZ
✖
✖
分享到微信
打开微信,点击底部的“发现”,
使用“扫一扫”即可将网页分享至微信联系人/群组。

货品号码1005391
fixed installation flexible use
PVC control cables

ÖPVC-JZ/OZ ARCTIC +UV SCHWARZ

01.01.04.05
Application

as UV- and cold resistant power, control and connecting cable in electrical facilities (e.g. in plant and machine building, in heating and air-conditioning technology or in frozen goods plants, cold stores), for fixed laying and flexible applications, without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms. Outdoor use but no laying underground

Selected item
Item no.: Description:
1005391 ÖPVC-OZ ARCTIC +UV 2X0,5 300/500 V, BLACK, -60 °C
Variants
Variant ▼
with gnye protective conductor ▼
Number of cores ▼
Cross section ▼
Item No. ↕️ Dimension ↕️ Outer-Ø [mm] nom. ↕️ Cu Index [kg/km] ↕️ Weight [kg/1.000] ↕️
PRODUCT INFO "ÖPVC-JZ/OZ ARCTIC +UV SCHWARZ"
SPECIAL FEATURES
* largely resistant to acids, bases and specified types of oil * increased cold resistant acc. to IEC 60811-1-4
REMARKS
* RoHS compliant * compliant with the 2014/35/EU Directive (''Low Voltage Directive'') CE
PRODUCT DETAILS
DESIGN
Conductor material bare copper strand Conductor class acc. to IEC 60228 cl. 5 Core insulation PVC, cold resistant Core identification acc. to DIN VDE 0293 black cores with white numerals with or without GNYE Stranding stranded in layers Inner sheath material Overall shield Outer sheath material PVC, cold resistant Sheath colour black, RAL 9005
ELECTRICAL PROPERTIES
Rated voltage AC IEC 300/500 V Testing voltage 3 kV Conductor resistance acc. to IEC 60228 cl. 5 Insulation resistance min. 20 MΩ x km Current carrying capacity acc. to DIN VDE
MECHANICAL & DYNAMIC PROPERTIES
Min. bending radius fixed 4 x d Min. bending radius moved 15 x d Traverse length (m) - drag chain Traverse speed (m/s) - drag chain Acceleration (m/s²) - drag chain Bending cycles (mln)
THERMAL PROPERTIES
Operat. temp. fixed min./max. [°C] -60 °C / +80 °C Operat. temp. moved min/max [°C] -40 °C / +70 °C Temp. at conductor in operation max [°C] +70 °C in operation; +140 °C in case of short-circuit
STANDARDS & APPROVALS
Standard similar to EN 50525-2-51 Approvals