垂询电话: 电子邮箱:
Variants
PRODUCT INFO "H05VVC4V5-K HAR"
SPECIAL FEATURES
* increased resistance to oil by special PVC outer sheath, largely resistant to acids and bases acc. to EN 50363-4-1
* additional mechanical protection by inner sheath
* EMC compliant shielding
* HAR-approval for Europe
REMARKS
* RoHS compliant
* Compliant with the 2014/35/EU Directive (''Low Voltage Directive'') CE
* LABS-free/silicone-free (during production)
* Special versions, other dimensions, cross-sections, wire and sheath colors are available on request.
PRODUCT DETAILS
DESIGN
Conductor material
bare copper strand
Conductor class
acc. to IEC 60228 cl. 5
Core insulation
PVC
Core identification
acc. to DIN VDE 0293 black cores with white numerals; G = with GNYE
Stranding
stranded in layers
Inner sheath material
PVC
Overall shield
copper braid tinned, coverage approx. 85 %
Outer sheath material
PVC
Sheath colour
grey, RAL 7001
ELECTRICAL PROPERTIES
Rated voltage AC IEC
Uo/U: 300/500 V
Testing voltage
3 kV
Conductor resistance
acc. to IEC 60228 cl. 5
Insulation resistance
min. 20 MΩ x km
Current carrying capacity
acc. to DIN VDE
MECHANICAL & DYNAMIC PROPERTIES
Min. bending radius fixed
6 x d
Min. bending radius moved
12,5 x d
Traverse length (m) - drag chain
Traverse speed (m/s) - drag chain
Acceleration (m/s²) - drag chain
Bending cycles (mln)
THERMAL PROPERTIES
Operat. temp. fixed min./max. [°C]
-40 °C / +70 °C
Operat. temp. moved min/max [°C]
-5 °C / +70 °C
Temp. at conductor in operation max [°C]
+70 °C in operation; +150 °C in case of short-circuit
STANDARDS & APPROVALS
Standard
EN 50525-2-51 / VDE 0285-525-2-51
Approvals
HAR