垂询电话: 电子邮箱:
Variants
PRODUCT INFO "KAWEFLEX® SERVO 2XSL(St)CHK... FRNC 0,6/1kV EMV"
SPECIAL FEATURES
* largely resistant to acids, bases and specified types of oil
* max. perm. current carrying capacity at 30 ° C ambient temperature.
* low operating capacity, low coupling resistance
* with UV-resistant, halogen-free outer sheath
* enables trouble-free operation of frequency converters through optimum EMC compliant shielding
* low capacitance enables longer cable lengths between motor and frequency converter
* increased power transmission with the same conductor cross-section compared to standard 2YSL(St)CY versions
REMARKS
* compliant with the 2014/35/EU Directive (''Low Voltage Directive'') CE
* LABS/silicon-free (during production)
* Special versions, e.g. for 120 °C max. conductor temperature, other dimensions, cross-sections, core and sheath colors are available on request.
PRODUCT DETAILS
DESIGN
Conductor material
bare copper strand
Conductor class
acc. to IEC 60228 cl. 5
Core insulation
XLPE
Core identification
acc. to DIN VDE 0293-308 coloured cores with GNYE
Stranding
stranded in layers
Inner sheath material
Overall shield
alu-lamin. polyester foil, metal side outside, cover. 100% under copper braid tinned
Outer sheath material
halogen-free compound
Sheath colour
black, RAL 9005
ELECTRICAL PROPERTIES
Rated voltage AC IEC
Uo/U 0,6/1 kV - highest permissible operating voltage Single phase and three-phase: 700/1200 V, DC operation: 900/1800 V
Testing voltage
4 kV
Conductor resistance
acc. to IEC 60228 cl. 5
Insulation resistance
min. 200 MΩ x km
Current carrying capacity
look at the table on the right side
MECHANICAL & DYNAMIC PROPERTIES
Min. bending radius fixed
≤ 12mm Ø: 5 x d; ≤ 20mm Ø: 7,5 x d; > 20mm Ø: 10 x d
Min. bending radius moved
≤ 12mm Ø: 10 x d; ≤ 20mm Ø: 15 x d; > 20mm Ø: 20 x d
Traverse length (m) - drag chain
Traverse speed (m/s) - drag chain
Acceleration (m/s²) - drag chain
Bending cycles (mln)
THERMAL PROPERTIES
Operat. temp. fixed min./max. [°C]
-40 °C / +80 °C
Operat. temp. moved min/max [°C]
-15 °C / +70 °C
Temp. at conductor in operation max [°C]
+ 90 °C in operation; +250 °C in case of short-circuit
STANDARDS & APPROVALS
Standard
Approvals
快捷服务 |
|||||