垂询电话: 电子邮箱:
Variants
PRODUCT INFO "DATEX-CY LI2YCY (TP) "
SPECIAL FEATURES
* twisted pairs
* largely resistant to acids, bases and specified types of oil
* LABS-/silicone-free (during production)
* recommended for EMC-applications
* suitable for maxi-termi-point applications by 7wire conductors <1 mm²
REMARKS
* RoHS compliant
* compliant with 2014/35/EU Directive (''Low Voltage Directive'') CE
* *: DATEX-CYv + UV LI2YCYv (TP), black outer sheath, for indoor and outdoor installation as well as for direct burial in the ground
* Special versions, other dimensions, cross-sections, core and sheath colors are available on request.
PRODUCT DETAILS
DESIGN
Conductor material
bare copper strand
Conductor class
7 wired
Core insulation
PE
Core identification
acc. to DIN 47100 different colours
Stranding
pairs stranded in layers
Inner sheath material
Overall shield
copper braid tinned; coverage approx. 85%
Outer sheath material
PVC
Sheath colour
grey, RAL 7032 (CY) and black, RAL 9005 (CYv)
ELECTRICAL PROPERTIES
Rated voltage AC IEC
250 V
Testing voltage
core/core: 2 kV; core/shield: 1 kV
Conductor resistance
loop: 0,22 mm² max. 186 Ω / km; 0,34 mm² max. 115 Ω / km; 0,50 mm² max. 78,4 Ω / km
Insulation resistance
min 5 GΩ x km
Current carrying capacity
acc. to DIN VDE, s. Techn. Guidelines
MECHANICAL & DYNAMIC PROPERTIES
Min. bending radius fixed
10 x d
Min. bending radius moved
15 x d
Traverse length (m) - drag chain
Traverse speed (m/s) - drag chain
Acceleration (m/s²) - drag chain
Bending cycles (mln)
THERMAL PROPERTIES
Operat. temp. fixed min./max. [°C]
-30 °C / +80 °C
Operat. temp. moved min/max [°C]
-5 °C / +70 °C
Temp. at conductor in operation max [°C]
STANDARDS & APPROVALS
Standard
similar to DIN VDE 0812
Approvals
快捷服务 |
|||||