垂询电话: 电子邮箱:
Variants
PRODUCT INFO "INDULINE® RE-2X(St)Yv-fl PIMF"
SPECIAL FEATURES
* more steady at higher frequencies and temperatures (+90°C) by XLPE core insulation (cross-linked PE)
* high crosstalk and low cable attenuation
* single element & overall shield
* largely resistant to acids, bases and usual oils
* Oil resitance: ICEA S-73-532 / NEMA WC 57-2004 § 6.9.3
* robust version with strenghthened outer sheath
* suitable for intrinsically safe systems zone 1+2 group II acc. IEC 60079-14
* Sunlight resitance: UL 1581 Section 1200
* flame-retardant acc. IEC 60332-1-2 and IEC 60332-3-24 (Cat. C)
REMARKS
* RoHS-compliant; conforms to 2014/35/EU Directive (''Low Voltage Directive'') CE
* Also available without reinforced outer sheath as RE-2X(St)Y-fl PIMF
* Special versions e.g. fire-resistant (mica), halogen-free, oil and chemical-resistant (lead sheath or GuardSheath - lead-free), BS 5308, MESC etc. can be manufactured on request >> also available as compensating cable > INDUTHERM < available
PRODUCT DETAILS
DESIGN
Conductor material
bare copper strand
Conductor class
7-wired construction acc. to IEC 60228 class 2
Core insulation
XLPE (cross-linked polyethylene)
Core identification
pairs: single-coloured with numerals: core A black, core B: white; triple: core A: white, core B: red, core C: black, core A and C with numerals
Stranding
pairs stranded in layers
Inner sheath material
Overall shield
plastic clad aluminium foil (24 μm) with subjacent tinned drain wire 0.5mm² (7x0.30 mm)
Outer sheath material
PVC
Sheath colour
black
ELECTRICAL PROPERTIES
Rated voltage AC IEC
300 V
Testing voltage
1,5 kV
Conductor resistance
0.5mm²: max.36.7Ω/km; 0.75mm²: max.25.0Ω/km; 1.3mm²: max.14.2Ω/km
Insulation resistance
min. 5 GΩ x km
Current carrying capacity
acc. to DIN VDE, s. Techn. Guidelines
MECHANICAL & DYNAMIC PROPERTIES
Min. bending radius fixed
7.5 x d
Min. bending radius moved
Traverse length (m) - drag chain
Traverse speed (m/s) - drag chain
Acceleration (m/s²) - drag chain
Bending cycles (mln)
THERMAL PROPERTIES
Operat. temp. fixed min./max. [°C]
-40°C / +70°C
Operat. temp. moved min/max [°C]
-5°C / +50°C
Temp. at conductor in operation max [°C]
STANDARDS & APPROVALS
Standard
EN 50288-7
Approvals
快捷服务 |
|||||