PRODUCT INFO "INDULINE® RE-2X(ST)YSWBY-FL"
SPECIAL FEATURES
* more steady at higher frequencies and temperatures (+90°C) by XLPE core insulation (cross-linked PE)
* high crosstalk and low cable attenuation
* largely resistant to acids, bases and usual oils
* Oil resitance: ICEA S-73-532 / NEMA WC 57-2004 § 6.9.3
* triple protection for high mechanical requirements and magnetic shield (oxidationproofed steel wire braid and additional inner sheath)
* suitable for intrinsically safe systems zone 1+2 group II acc. IEC 60079-14
* Sunlight resitance: UL 1581 Section 1200
* flame-retardant acc. IEC 60332-1 and IEC 60332-3-24 (Cat. C)
REMARKS
* RoHS-compliant, compliant with the 2014/35/EU Directive (''Low Voltage Directive'') CE
* Special versions e.g. fire-resistant (mica), halogen-free, oil and chemical-resistant (lead sheath or GuardSheath - lead-free), BS 5308, MESC etc. can be manufactured on request >> also available as compensating cable > INDUTHERM <.
PRODUCT DETAILS
DESIGN
Conductor material
bare copper strand
Conductor class
7-wired construction acc. to IEC 60228 cl. 2
Core insulation
XLPE (cross-linked polyethylene)
Core identification
pairs: single-coloured with numerals: core A black, core B: white; triple: core A: white, core B: red, core C: black, core A and C with numerals
Stranding
pairs stranded in layers
Inner sheath material
PVC, black
Overall shield
steel wire braid, galvanized (SWB)
Outer sheath material
PVC
Sheath colour
black or blue RAL 5015 for intrinsically safe systems
ELECTRICAL PROPERTIES
Rated voltage AC IEC
300 V
Testing voltage
1,5 kV
Conductor resistance
0.5mm²: max.36.7 Ω/km; 0.75mm²: max.25.0 Ω/km; 1.3mm²: max.14.2 Ω/km
Insulation resistance
min. 5 GΩ x km
Current carrying capacity
acc. to DIN VDE, s. Techn. Guidelines
MECHANICAL & DYNAMIC PROPERTIES
Min. bending radius fixed
10 x d
Min. bending radius moved
Traverse length (m) - drag chain
Traverse speed (m/s) - drag chain
Acceleration (m/s²) - drag chain
Bending cycles (mln)
THERMAL PROPERTIES
Operat. temp. fixed min./max. [°C]
-40°C / +70°C
Operat. temp. moved min/max [°C]
- 5°C / +50°C
Temp. at conductor in operation max [°C]
STANDARDS & APPROVALS
Standard
EN 50288-7
Approvals