ASi-BUS Aktor Sensor Interface - HF UL/CSA
✖
✖
分享到微信
打开微信,点击底部的“发现”,
使用“扫一扫”即可将网页分享至微信联系人/群组。

货品号码2003713
fixed installation flexible use
BUS | FIELDBUS cables for industrial & process automation

ASi-BUS Aktor Sensor Interface - HF UL/CSA

03.10.06.02
Application

as fieldbus cables for ASi (Actuator Sensor Interface) systems, in the field of factory automation, for connecting devices to the lowest field level (sensors, actuators), for high flexible applications (e.g. power chains, gantry robots, pick&place units, conveyors, machine tools, automated production systems, etc.). Data & energy are transmitted via an unscreened, geometrically coded two-core flat cable. Standard acc. to EN 50295 / IEC 62026

Selected item
Item no.: Description:
2003713 ASi-BUS SK-PUR FRNC UL/CSA 2X1,5 YELLOW, cURus AWM
Variants
Variant ▼
with gnye protective conductor ▼
Number of cores ▼
Cross section ▼
Item No. ↕️ Dimension ↕️ Outer-Ø [mm] nom. ↕️ Cu Index [kg/km] ↕️ Weight [kg/1.000] ↕️
PRODUCT INFO "ASi-BUS Aktor Sensor Interface - HF UL/CSA"
SPECIAL FEATURES
- low adhesion - special geometry prevents incorrect contacting (reverse polarity protection) - simple & quick installation without tools (piercing technology) - oil-resistant: acc. to DIN EN 60811-2-1 - UV-resistant
REMARKS
- RoHS compliant - compliant with the 2014/35/EU Directive (''Low Voltage Directive'') CE - LABS/silicone-free (during production) - FRNC: Flame Retardant Non Corrosive, halogen-free - LD - Long Distance
PRODUCT DETAILS
DESIGN
Conductor material copper strand tinned Conductor class super fine wire, acc. to IEC 60228 cl. 6 Core insulation TPE Core identification blue, brown Stranding Inner sheath material Overall shield Outer sheath material PUR Sheath colour yellow RAL 1023 (YE) or black RAL 9005 (BK)
ELECTRICAL PROPERTIES
Rated voltage AC IEC 300 V (not for high voltage purposes) Testing voltage 2 kV Conductor resistance 13,7 Ω/km - 1,5mm²; 8,21 Ω/km 2,5 mm² Insulation resistance Current carrying capacity
MECHANICAL & DYNAMIC PROPERTIES
Min. bending radius fixed 12 mm Min. bending radius moved 60 mm Traverse length (m) - drag chain max. 5 m Traverse speed (m/s) - drag chain Acceleration (m/s²) - drag chain max. 3 m/s² Bending cycles (mln)
THERMAL PROPERTIES
Operat. temp. fixed min./max. [°C] -40°C / +80°C Operat. temp. moved min/max [°C] -30°C / +70°C Temp. at conductor in operation max [°C]
STANDARDS & APPROVALS
Standard Approvals UL/CSA - cURus 300V, 80 °C, AWM

点击查看更多射频微波产品