垂询电话: 电子邮箱:
Variants
PRODUCT INFO "KAWEFLEX® 6110 TRAY SK-PVC UL/CSA"
SPECIAL FEATURES
* UL/CSA approval
* low adhesion, silicone-free
* increased oil-resistant special PVC outer sheath, largely resistant to greases, coolants and lubricants acids and alkalis - oil-resistant according to UL OIL RES I
* water resistant according to UL wet approval 75°C
* Flame retardant acc. to IEC 60332-1-2, CSA FT4, UL Vertical Tray Flame Test
* UV-resistan
REMARKS
* RoHS compliant
* compliant with the 2014/35/EU Directive ("Low Voltage Directive") CE
* in accordance with NFPA 79 and NEC "National Electrical Code" Art. 336, 392, 501
PRODUCT DETAILS
DESIGN
Conductor material
bare copper strand
Conductor class
acc. to IEC 60228 cl. 6
Core insulation
PVC
Core identification
acc. to DIN VDE 0293 black cores with white numerals; G = GNYE
Stranding
cores stranded in layers
Inner sheath material
Overall shield
Outer sheath material
PVC
Sheath colour
black RAL 9005
ELECTRICAL PROPERTIES
Rated voltage AC IEC
IEC: 300/500 V; UL/CSA: 600V (TC, MTW, CIC), 1.000V (WTTC, AWM)
Testing voltage
6 kV
Conductor resistance
at +20 °C acc. to IEC 60228 cl. 6
Insulation resistance
at +20 °C ≥ 20 MΩ x km
Current carrying capacity
acc. to DIN VDE
MECHANICAL & DYNAMIC PROPERTIES
Min. bending radius fixed
4 x d
Min. bending radius moved
7,5 x d < 10m TL | 10 x d ≥ 10m TL
Traverse length (m) - drag chain
max. 25 m
Traverse speed (m/s) - drag chain
Acceleration (m/s²) - drag chain
max. 10 m/s²
Bending cycles (mln)
THERMAL PROPERTIES
Operat. temp. fixed min./max. [°C]
-40 °C / +90 °C
Operat. temp. moved min/max [°C]
-5 °C / +90 °C
Temp. at conductor in operation max [°C]
STANDARDS & APPROVALS
Standard
UL 1277, UL 1063 (MTW), NEC 336.10 (7) class1, Div. 2 acc. NEC Art. 336, 392, 501
Approvals
UL/CSA - cULus & cURus 1.000V, 90°C (AWM, WTTC) and cULus & cURus 600V, 90°C (TC-ER, MTW, CIC)