垂询电话: 电子邮箱:
Variants
PRODUCT INFO "NYCY 0,6/1kV"
SPECIAL FEATURES
* 0,6/1 kV operating voltage, 4 kV testing voltage
* UV-resistant
* no hood termination necessary when laying in dry rooms
* use of concentric conductor as shield, neutral conductor or earth conductor is permitted but not as outer conductor
* free from lacquer damaging substances and silicone (during production)
REMARKS
* RoHS compliant
* compliant with 2006/95/EC Directive ("Low Voltage Directive") CE.
* available with blue outer sheath for intrinsically safe systems on request
* Special versions, other dimensions, cross-sections, core and sheath colors are available on request
PRODUCT DETAILS
DESIGN
Conductor material
bare copper conductor
Conductor class
acc. to DIN VDE 0295 class 1 resp. IEC 60228 cl. 1
Core insulation
PVC
Core identification
single core black; multi core acc. to VDE 0207 part 4
Stranding
multi core stranded in layers
Inner sheath material
filler sheath
Overall shield
concentric conductor of blank round copper wires
Outer sheath material
PVC
Sheath colour
black
ELECTRICAL PROPERTIES
Rated voltage AC IEC
Uo/U: 0,6/1 kV
Testing voltage
4 kV
Conductor resistance
at +20 °C acc. to DIN VDE 0295 class 1 resp. IEC 60228 cl. 1
Insulation resistance
Current carrying capacity
acc. to DIN VDE, see Technical Guidelines
MECHANICAL & DYNAMIC PROPERTIES
Min. bending radius fixed
single core: 15 x d ; multi core: 12 x d
Min. bending radius moved
Traverse length (m) - drag chain
Traverse speed (m/s) - drag chain
Acceleration (m/s²) - drag chain
Bending cycles (mln)
THERMAL PROPERTIES
Operat. temp. fixed min./max. [°C]
-40 °C / +70 °C
Operat. temp. moved min/max [°C]
- 5 °C / +50 °C
Temp. at conductor in operation max [°C]
+ 70 °C in operation; +160 °C in case of short-circuit
STANDARDS & APPROVALS
Standard
acc. to DIN VDE 0276-603 and IEC 60502
Approvals
VDE
快捷服务 |
|||||