垂询电话: 电子邮箱:
Variants
PRODUCT INFO "NYCWY 0,6/1kV"
SPECIAL FEATURES
* 0,6/1 kV operating voltage 4 kV testing voltage
* UV-resistant
* no hood termination necessary when laying in dry rooms
* use of concentric undulated CEANDER copper conductor as shield, neutral conductor or earth conductor is permitted but not as outer conductor
* any branch connection possible because of non-engraving of concentric CEANDER conductor (CW)
* free from lacquer damaging substances and silicone (during production)
REMARKS
* RoHS compliant
* conforms to the 2006/95/EC Directive ("Low Voltage Directive") CE.
* available with blue outer sheath for intrinsically safe systems and as NAYCWY (with aluminum conductor) on request
* Special versions, other dimensions, cross-sections, core and sheath colors are available on request.
PRODUCT DETAILS
DESIGN
Conductor material
bare copper conductor
Conductor class
acc. to DIN VDE 0295 class 1 or 2 resp. IEC 60228 class 1 or 2
Core insulation
PVC
Core identification
acc. to VDE 0293-308
Stranding
cores stranded in layers
Inner sheath material
filler sheath
Overall shield
concentric conductor of blank round copper-wires ceander form
Outer sheath material
PVC
Sheath colour
black
ELECTRICAL PROPERTIES
Rated voltage AC IEC
Uo/U: 0,6/1 kV
Testing voltage
4 kV
Conductor resistance
at +20 °C acc. to DIN VDE 0295 class 1 oder 2 resp. IEC 60228 class 1 or 2
Insulation resistance
Current carrying capacity
acc. to DIN VDE, see Technical Guidelines
MECHANICAL & DYNAMIC PROPERTIES
Min. bending radius fixed
single core: 15 x d ; multi core: 12 x d
Min. bending radius moved
Traverse length (m) - drag chain
Traverse speed (m/s) - drag chain
Acceleration (m/s²) - drag chain
Bending cycles (mln)
THERMAL PROPERTIES
Operat. temp. fixed min./max. [°C]
-40 °C / +70 °C
Operat. temp. moved min/max [°C]
- 5 °C / +50 °C
Temp. at conductor in operation max [°C]
+ 70 °C in operation; +160 °C in case of short-circuit
STANDARDS & APPROVALS
Standard
acc. to DIN VDE 0276-603 and IEC 60502
Approvals
VDE